Sec. 29.1183 - Lines, fittings, and components.
(a) Except as provided in paragraph (b) of this section, each line,
fitting, and other component carrying flammable fluid in any area subject
to engine fire conditions and each component which conveys or contains
flammable fluid in a designated fire zone must be fire resistant, except
that flammable fluid tanks and supports in a designated fire zone must be
fireproof or be enclosed by a fireproof shield unless damage by fire to
any non-fireproof part will not cause leakage or spillage of flammable
fluid. Components must be shielded or located so as to safeguard against
the ignition of leaking flammable fluid. An integral oil sump of less than
25-quart capacity on a reciprocating engine need not be fireproof nor be
enclosed by a fireproof shield.
(b) Paragraph (a) of this section does not apply to --
(1) Lines, fittings, and components which are already approved as part
of a type certificated engine; and
(2) Vent and drain lines, and their fittings, whose failure will not
result in or add to, a fire hazard.